2003-10-14 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE PLANS AND PANEL
 SCHEDULE.
 PLEASE SEE THAT PANEL "A" AND "C" SHOW
 A/C UNITS (#6).
 PLEASE ALSO SEE THAT PLANS ONLY SHOW
 5 A/C SYSTEMS AND PANEL SCHEDULES SHOW
 6? PLEASE CORRELATE AND/OR CLARIFY.
  
 2)NOTE: PLEASE PROVIDE ALL LICENSE
 INFORMATION ON TITLE BLOCK REQ'D UNDER
 FAC 61G15-23.002 AND FS 471
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  