| Date |
Text |
| 2003-01-25 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A2 DEMO NOTES #'S 4,5,& 9, ALL |
| | PIPES CAPPED OFF IN FLOOR OR WALLS SHALL |
| | BE INSPECTED PRIOR TO COVERING. |
| | 2) SHT A2 PLEASE CLAIRFY PREP AREAS. IF |
| | SERVING FOOD, PLEASE NOTE THAT PLANS MAY |
| | HAVE TO BE ROUTED TO THE HEALTH DEPT. IF |
| | THESE ARE BREAK ROOMS, SINKS SHALL COM- |
| | PLY WITH SECTION 11-4.24 AND ALL SUB- |
| | SECTIONS AND A DETAIL WILL BE REQUIRED. |
| | 3) SHT A3 PLEASE SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | 1/2 AREA FOR ALL VERTICAL WALLS INCLUD- |
| | ING PARAPET WALLS IN CALCULATIONS. INDI- |
| | CATE LOCATION, NUMBER, & SIZE OF ALL |
| | DOWNSPOUTS AND IF ROOF IS FLAT OR PITCH- |
| | ED. |
| | 4) SECTION 11-4.1.2(6) IF TOILET FACIL- |
| | ITIES ARE PROVIDED ON A SITE THEN EACH |
| | SUCH PUBLIC OR COMMON USE TOILET FACIL- |
| | ITY SHALL COMPLY WITH 11-4.22. IF BATH- |
| | ING FACILITIES ARE PROVIDED ON A SITE, |
| | THEN EACH SUCH PUBLIC OR COMMON USE |
| | BATHING FACILITY SHALL COMPLY WITH |
| | 11-4.23 |
| | 5) SHT A4 TOILET ROOMS SHALL COMPLY WITH |
| | SECTION 11-4.22 & ALL SUBSECTIONS. |
| | PLEASE SHOW ON DETAILS. (SEE SECTIONS |
| | 11-4.16, 11-4.18, SHOW 5'TURNING RADIUS |
| | IN EACH TOILET ROOM, SEE FIG.28, DOORS |
| | SHALL NOT OPEN INTO ANY CLEAR FLOOR |
| | SPACE OR TURNING RADIUS ECT,) |
| | 6) SHT A4 SHOWER STALLS SHALL COMPLY |
| | WITH 11-4.21 AND ALL SUBSECTIONS. PLEASE |
| | SHOW ON DETAILS. |
| | 7) SHT P-2 SANITARY RISER DIAGRAM, |
| | DRINKING FOUNTAIN IS NOT SHOWN. |
| | 8) SHT P-2 WATER RISER DIAGRAM, DRINKING |
| | FOUNTAIN IS NOT SHOWN. WATER HAMMER ARR- |
| | ESTORS ARE REQUIRED AT WASH MACHINE, ICE |
| | MAKER AND DISHWASHER IF PROVIDED. SECT. |
| | 604.9 |
| | 9) SHT P-3 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL REQUIRED. SEC 607.3.2 |
| | PLEASE SHOW EXPANSION TANK. |
| | 10) SHT P-3 GENERAL NOTES #16, AIR |
| | CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| | REFERENCE. |
| | 11) SHT P-1 SEPARATE GAS PERMIT REQUIRED |
| | SEE FOLLOWING LIST OF GAS APPLICATION |
| | REQUIREMENTS. |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 10. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | 11. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |