| Plan Review Notes For Permit 03011201 |
| Permit Number |
03011201 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-03 00:00:00 | DENIED:MECHANICAL PERMIT 03011203 | | | | | | 1.PLAN SHEET M-1, CONFERENCE RM 1 & 2 | | | DOES NOT INDICATE RETURN AIR OR TRANSFER | | | AIR.2001 FBC(M) 601.4 | | | | | | 2.FRESH AIR INTAKES SHALL BE LOCATED | | | FROM ANY NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, STREETS, ALLEYS, OR PARKING LOTS. | | | 2001 FBC(M) 401.5.1 | | | | | | 3.EXHAUST OPENINGS SHALL BE LOCATED | | | AS NOT TO CREATE A NUISANCE.EXHAUST | | | AIR SHALL NOT BE DIRECTED ONTO WALKWAYS. | | | | | | 4.PLAN SHEET M-1, INDICATES AHU-3 & 2 | | | SERVING THE SAME AREA, AS PER 2001 FBC | | | (M) 606.2.2 - WHERE MULTIPLE AHU'S WITH | | | A DESIGN CAPACITY GREATER THAN 2,000 CFM | | | SHALL BE PROVIDED WITH DUCT SMOKE | | | DETECTORS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|