2003-02-03 00:00:00DENIED:MECHANICAL PERMIT 03011203
  
 1.PLAN SHEET M-1, CONFERENCE RM 1 & 2
 DOES NOT INDICATE RETURN AIR OR TRANSFER
 AIR.2001 FBC(M) 601.4
  
 2.FRESH AIR INTAKES SHALL BE LOCATED
 FROM ANY NOXIOUS CONTAMINANT, SUCH AS
 VENTS, STREETS, ALLEYS, OR PARKING LOTS.
 2001 FBC(M) 401.5.1
  
 3.EXHAUST OPENINGS SHALL BE LOCATED
 AS NOT TO CREATE A NUISANCE.EXHAUST
 AIR SHALL NOT BE DIRECTED ONTO WALKWAYS.
  
 4.PLAN SHEET M-1, INDICATES AHU-3 & 2
 SERVING THE SAME AREA, AS PER 2001 FBC
 (M) 606.2.2 - WHERE MULTIPLE AHU'S WITH
 A DESIGN CAPACITY GREATER THAN 2,000 CFM
 SHALL BE PROVIDED WITH DUCT SMOKE
 DETECTORS.
  