Plan Review Notes
Plan Review Notes For Permit 03011201
Permit Number 03011201
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-01-23 00:00:001) THE NEW ROLLING CHAIN-LINK GATE
 WHEN OPENED MUST PROVIDE AT LEAST
 20 FEET IN CLEAR WIDTH.
  
 2) IT APPEARS THAT ADDITIONAL EXIT
 SIGNS WILL BE NEEDED. IN SOME LOCALES,
 EXIT SIGNS APPEAR TO BE BLOCKED
 VISUALLY BY WALLS.
  
 3) IF THE EAST ELEVATION IS THE ADDRESS
 SIDE OF THE BUILDING, THEN THE ADDRESS
 SHALL BE BE POSTED WITH A MINIMUM OF
 6" LETTERS.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910