| Plan Review Notes For Permit 03011201 |
| Permit Number |
03011201 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-23 00:00:00 | 1) THE NEW ROLLING CHAIN-LINK GATE | | | WHEN OPENED MUST PROVIDE AT LEAST | | | 20 FEET IN CLEAR WIDTH. | | | | | | 2) IT APPEARS THAT ADDITIONAL EXIT | | | SIGNS WILL BE NEEDED. IN SOME LOCALES, | | | EXIT SIGNS APPEAR TO BE BLOCKED | | | VISUALLY BY WALLS. | | | | | | 3) IF THE EAST ELEVATION IS THE ADDRESS | | | SIDE OF THE BUILDING, THEN THE ADDRESS | | | SHALL BE BE POSTED WITH A MINIMUM OF | | | 6" LETTERS. | | | | | | 4) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|