| | BUILDING PLAN REVIEW |
| | PERMIT: 03011198 |
| | ADD:537 CLEMATIS STREET |
| | CONT: COMPLETE PROPERTY MANAGEMENT |
| | TEL: (561)626-2778 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) NEW ADDRESSES TO BE USED! |
| | A) 535 CLEMATIS ST- SITE ADDRESS |
| | B) 537 CLEMATIS ST- NEW FIRST FL TENANT |
| | C) 539 CLEMATIS ST- 2ND FL TENANT |
| | D) 541 CLEMATIS ST- RESTAURANT |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSINGREPORTS: |
| | A) FIXED WINDOWS/ LARGE MISSLE IMPACT. |
| | RESISTANCE |
| | B) MULLION (HORIZONTAL) W/ LARGE |
| | MISSLE IMPACT RESISTANCE |
| | C) EXTERIOR METAL DOOR/ FRAME EXTERIOR |
| | SWING. REPORT SUBMITTED RESIDENTIAL |
| | INSWING. |
| | |
| | 3)1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 4)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 5) 1707.4.3 EACH EXTERIOR DOOR |
| | ASSEMBLY NOT COVERED BY 1707.4.2 |
| | (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| | ED FOR A PERIOD EQUAL TO THE QUANITY |
| | 3600/ V WHERE THE TIME PERIOD IS IN |
| | SECTIONS AND V IS IN MILES PER HR TAKEN |
| | FROM FIGURE 1606. THE TIME PERIOD SHALL |
| | ALSO INCLUDE A 10 SECOND PERIOD AT A |
| | LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| | PRESSURE. DADE COUNTY & SBCCI REPORTS |
| | ARE ACCEPTED. |
| | |
| | 6)705.7.1 JOINTS INSTALLED IN OR BE- |
| | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES |
| | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| | ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE RE- |
| | QUIRED FIRE RESISTANCE RATING OF THE |
| | WALL, FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | |
| | 7)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | MECHANIACAL PLANS INDICATE THAT THE AIR |
| | HANDLER IS TO BE HUNG FROM THE CONCRETE |
| | DECK ABOVE. SHEET A-3.00 INDICATES WOOD |
| | FLOOR TRUSSES, ENGINEER LETTER FOR THE |
| | ADDITIONAL LOADS BEING TRANSFERRED TO |
| | THE WOOD FLOOR TRUSSES. WILL ADDITIONAL |
| | BACKING BE REQUIRED? WHAT TYPE OF FASTEN |
| | ER IS TO BE USED TO MAKE THE CONNECTION |
| | TO THE 1/2" SUSPENTION RODS? |
| | |
| | 8)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 9)FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | |
| | 10)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |