| Plan Review Notes For Permit 03011187 |
| Permit Number |
03011187 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-03 00:00:00 | DENIED: | | | | | | CLARIFY MAKE-UP AIR TO NEW BATHROOM. | | | THE AMOUNT OF SUPPLY AIR SHALL BE | | | APPROXIMATELY EQUAL TO THE AMOUNT OF | | | AIR EXHAUSTED.2001 FBC(M) 403.1 | | | | | | PLAN SHEET A.1 WALL LEGEND "EXISTING 1 | | | HR" RATED CONSTRUCTION.FIRE DAMPERS | | | ARE REQUIRED ON DUCTS PENETRATING WALLS | | | HAVING A FIRE RESISTANCE RATING OF 1 HR | | | OR MORE.2001 FBC(M) 607.1.2 #1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|