| Plan Review Notes For Permit 03011180 |
| Permit Number |
03011180 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-01-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) PERMIT ISSUED IN ERROR - NO PLAN RE- | | | VIEW FOR GAS PRIOR TO ISSUANCE. | | | 2) FOLLOWING INFORMATION REQUIRED FOR | | | REVISION. | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | B. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. WATER HEATER NOT | | | SHOWN ON PLAN. | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | D. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|