| Plan Review Notes For Permit 03011168 |
| Permit Number |
03011168 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-17 00:00:00 | DENIED: | | | | | | 1. ORIGINAL PLANS SUBMITTED AND APPROVED | | | ARE SIGNED & SEALED BY ARCHITECT.ANY | | | CHANGES TO THESE PLANS MUST BE DONE BY | | | THE ARCHITECT AND BE SIGNED AND SEALED. | | | | | | 2. PLEASE NOTE THE SUPPLY DUCT TO THE | | | DISTRIBUTION BOX IS NOT SIZED. | | | | | | 3. THE EQUIPMENT SUBMITTED & APPROVED | | | IS GOODMAN, NO MANUFACTURER IS SHOWN | | | ON THE PLANS SUBMITTED. | | | | | | 4. THE APPROVED ENERGY & MANUAL J CALCS | | | DO NOT MATCH THE REVISED EQUIPMENT | | | SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|