| Plan Review Notes For Permit 03011168 |
| Permit Number |
03011168 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT 5 SANITARY RISER DIAGRAM, ONLY | | | THE FIXTURES WITHIN THE BATHROOM GROUP | | | SHALL CONNECT TO THE WET-VENTED HORIZON- | | | TAL BRANCH DRAIN. THE WASH MACHINE AND | | | KITCHEN SINK SHALL TIE IN DOWNSTREAM OF | | | THE BATHROOM GROUP. SECTION 909.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|