Plan Review Notes
Plan Review Notes For Permit 03011066
Permit Number 03011066
Review Stop B
Sequence Number 2
Notes
Date Text
2003-02-25 00:00:00BUILDING DENIED
  
 1) PLEASE REVISE NOTE #11 UNDER PLAN
 NOTES ON C1 TO INDICATE THAT HURRICANE
 PANELS ARE REQUIRED IN WIND BOURNE
 DEBRIS REGIONS.
  
 2) INDICATE ON C1 NOTE #15 UNDER
 FRAMING NOTES THAT HIGH RIB METAL LATHE
 IS REQUIRED TO BE FASTENED AT EACH RIB
 (4"O.C.). SEE FBC 2504.2.2 & ASTM C 1063
  
 3) SPECIFY ON THE PLANS THAT THE WWM IN
 THE SLAB IS REQUIRED TO BE SUPPORTED ON
 APPROVED MATERIAL AT MAXIMUM OF 3 FEET
 ON CENTER. SEE FBC 1909.3
  
 4) INDICATE THE INTERNAL PRESSURE
 COEFFICIENT ON THE PLANS. SPECIFY IF THE
 STRUCTURE IS DESIGNED AS ENCLOSED, OPEN,
 OR PARTICALLY ENCLOSED.
  
 5) THE CONDITIONED FLOOR AREA GIVEN ON
 THE ENERGY CALCULATIONS IS 2464 SQFT AND
 THE PLANS LIST 2526 SQFT. PLEASE CORRECT
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202