| Plan Review Notes For Permit 03011066 |
| Permit Number |
03011066 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-02-25 00:00:00 | BUILDING DENIED | | | | | | 1) PLEASE REVISE NOTE #11 UNDER PLAN | | | NOTES ON C1 TO INDICATE THAT HURRICANE | | | PANELS ARE REQUIRED IN WIND BOURNE | | | DEBRIS REGIONS. | | | | | | 2) INDICATE ON C1 NOTE #15 UNDER | | | FRAMING NOTES THAT HIGH RIB METAL LATHE | | | IS REQUIRED TO BE FASTENED AT EACH RIB | | | (4"O.C.). SEE FBC 2504.2.2 & ASTM C 1063 | | | | | | 3) SPECIFY ON THE PLANS THAT THE WWM IN | | | THE SLAB IS REQUIRED TO BE SUPPORTED ON | | | APPROVED MATERIAL AT MAXIMUM OF 3 FEET | | | ON CENTER. SEE FBC 1909.3 | | | | | | 4) INDICATE THE INTERNAL PRESSURE | | | COEFFICIENT ON THE PLANS. SPECIFY IF THE | | | STRUCTURE IS DESIGNED AS ENCLOSED, OPEN, | | | OR PARTICALLY ENCLOSED. | | | | | | 5) THE CONDITIONED FLOOR AREA GIVEN ON | | | THE ENERGY CALCULATIONS IS 2464 SQFT AND | | | THE PLANS LIST 2526 SQFT. PLEASE CORRECT | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|