Plan Review Notes
Plan Review Notes For Permit 03011066
Permit Number 03011066
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-05 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PLEASE REVISE NOTE #11 UNDER PLAN
 NOTES ON C1 TO INDICATE THAT HURRICANE
 PANELS ARE REQUIRED IN WIND BOURNE
 DEBRIS REGIONS.
  
 4) PLEASE INDICATE ON C1 NOTE #15 UNDER
 FRAMING NOTES THAT HIGH RIB METAL LATH
 IS REQUIRED TO BE FASTENED AT EACH RIB
 (4"OC) PER ASTM C 1063 AND FBC 2504.2.2
  
 5) SPECIFY ON THE PLANS THAT THE WWM IN
 THE SLAB IS REQUIRED TO BE SUPPORTED ON
 APPROVED MATERIAL AT A MAXIMUM OF THREE
 FEET ON CENTER PER FBC 1909.3.
  
 6) THE FOUNDATION FOR THE PRIVACY WALL
 ENCROACHS ON THE ADJACENT LOT AT THE
 ZERO LOT LINE. PLEASE CORRECT.
  
 7)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE INTERNAL PRESSURE
 INTERNAL PRESSURE COEFFICIENT ON THE
 PLANS.
  
 8) DETAIL 10 ON A5 IS INDICATED AT THE
 WRONG TRUSS ON THE FRAMING PLAN.
  
 9) THE CONDITIONED FLOOR AREA GIVEN ON
 THE ENERGY CALCULATIONS IS 2464 SQFT AND
 THE PLANS LIST 2526 SQFT. PLEASE CORRECT
  
 10) THE ENERGY CALCULATIONS INDICATE
 THAT THE CREDIT FOR CEILING FANS IS
 BEING TAKEN. PLEASE INDICATE ON THE
 PLANS THE LOCATION AND SIZE OF THE FANS
 BASED ON THE ROOM SIZE PER FBC CHAPTER
 13 TABLE 6-6.
  
 11) THE WALL SECTION ON A4 SPECIFIES
 INSULATION WITH A MINIMUM OF R 3.5 AND
 THE ENERGY CALCS. LIST R 4.2. PLEASE
 CORRECT.
  
 12) PROVIDE THE UL LISTING INFORMATION
 AND MANUFACTURER'S SPECIFICATIONS FOR
 THE ONE HOUR FIRE RATED GLASS BLOCKS.
  
 13) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS DO NOT
 MATCH THE ARCHITECTURAL DRAWINGS. PLEASE
 REVISE.
  
 14) THE PRODUCT APPROVAL FOR THE DOUBLE
 OUTSWING FRONT DOORS IS A PRELIMINARY
 NOA. THE DRAWINGS DO NOT HAVE THE
 RENEWAL STAMP WITH THE NEW NUMBER.
 PLEASE SUBMIT THE FINAL NOA.
  
 15) THE PRODUCT APPROVALS SUBMITTED FOR
 THE STRUCTURAL MULLIONS DO NOT HAVE
 ADEQUATE DESIGN PRESSURES LISTED FOR THE
 MULLION BETWEEN THE 12'X8' SLIDING GLASS
 DOOR AND THE FIXED GLASS WINDOWS. PLEASE
 SUBMIT APPROPRIATE PRODUCT APPROVAL OR
 ENGINEERED ASSEMBLY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202