Plan Review Notes
Plan Review Notes For Permit 03011058
Permit Number 03011058
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-04 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PLEASE REVISE NOTE 11 ON C1 UNDER
 PLAN NOTES TO " IN WIND BOURNE DEBRIS
 REGIONS PROVIDE HURRICANE SHUTTERS ..."
  
 4) THREE EIGHTS INCH (HI-RIB) METAL LATH
 IS REQUIRED TO BE FASTENED AT EACH RIB
 (4" O.C.) PER FBC 2405.2.2 & ASTM C 1063
 PLEASE REVISE NOTE 15 ON C1 UNDER
 FRAMING NOTES.
  
 5) THE PRIVACY WALL FOOTING ENCROACHES
 ONTO THE ADJOINING LOT AT THE ZERO LOT
 LINE. PLEASE CORRECT.
  
 6) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED AT THE ZERO LOT LINE. PLEASE
 SPECIFY THIS ON THE PLANS AND SUBMIT THE
 UL LISTING AND MANUFACTURER'S
 INFORMATION FOR FIRE RATING.
  
 7) SPECIFY ON THE PLAN THAT THE BONUS
 ROOM, WHICH DOES NOT HAVE AN EGRESS
 WINDOW IS NOT TO BE USED AS A SLEEPING
 ROOM.
  
 8) THE WALL SECTION ON A4 SPECIFIES A
 MINIMUM R3.5 INSULATION AND THE ENERGY
 CALCULATIONS LIST THE WALL INSULATION AS
 R4.2. PLEASE CORRECT.
  
 9) THE DETAIL FOR THE GIRDER AT THE REAR
 COVERED PORCH IS LISTED AS DET. 15/A5 ON
 SHEET A6 AND IT APPEARS THAT IT SHOULD
 BE 12/A5. PLEASE CLARIFY.
  
 10) THE DISTANCES TO THE PROPERTY LINES
 FROM THE STRUCTURE IS NOT INDICATED ON
 THE SITE PLAN.
  
 11) THE PRODUCT APPROVALS THAT WERE
 SUBMITTED FOR THE FRONT DOORS IS A
 PRELIMINARY NOA THE DRAWINGS DO NOT HAVE
 THE RENEWAL STAMP WITH THE NEW NOA #.
 PLEASE SUBMIT FINAL NOA.
  
 12) THE KEY PLAN AND INSTALLATION
 SCHEDULE SUBMITTED DOES NOT CORRESPOND
 WITH THE ARCHITECTURAL PLANS. SUBMIT THE
 CORRECT INFORMATION.
  
 13) THE PRODUCT APPROVALS SUBMITTED FOR
 THE STRUCTURAL MULLIONS WILL NOT WORK
 BETWEEN THE TWELEVE FOOT SLIDING GLASS
 DOOR AND THE FIXED WINDOW ABOVE. THE
 CHARTS DO NOT LIST DESIGN PRESSURES FOR
 A 144" MULLION LENGTH AND A 120" OPENING
 WIDTH. ANOTHER PRODUCT APPROVAL OR AN
 ENGINEERED SYSTEM WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202