| 2003-03-15 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03010851 |
| | ADD: 4500 S DIXIE HWY |
| | CONT: TUSCANI |
| | TEL: (561)586-3808 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) 11-4.1.2 VERTICAL ACCESSIBILITY, |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED |
| | TO RELIEVE THE OWNER OF ANY BUILDING, |
| | SSTRUCTURE OR FACILITY FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| | LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| | GRADE LEVEL. |
| | 11-4.1.3(1) AT LEAST ONE ACCESSIBLE |
| | ROUTE COMPLYING WITH 11-4.3 SHALL |
| | CONNECT ACCESSIBLE BUILDING OR FACILITY |
| | ENTRANCES WITH ALL ACCESSIBLE SPACES |
| | AND ELEMENTS WITHIN THE BUILDING OR |
| | FACILITY. |
| | 11-4.1.6 ACCESSIBLE BUILDINGS: |
| | ALTERATIONS 1(B) IF EXISTING ELEMENTS, |
| | SPACES OR COMMON AREAS ARE ALTERED, THEN |
| | SUCH ALTERED ELEMENTS, SPACES, FEATURES, |
| | OR AREA SHALL COMPLY WITH THE APPLICABLE |
| | PROVISIONS OF 11-4.1.1 TO 11-4.1.3 |
| | MINIMUM REQUIREMENTS FOR NEW CONSTRUC- |
| | TION. |
| | |
| | ADDITIONAL INFORMATION SHALL BE RE- |
| | QUIRED FOR THE USE OF THE VERTICAL |
| | PLATFORM LIFT.THE FOLLOWING WILL BE |
| | REQUIRED: |
| | (A) A NOTIRIZED LETTER FROM THE SCHOOL |
| | ADMINISTRATOR ATESTING THAT THE VER- |
| | TICAL LIFT WILL BE AVAILABLE FOR ANY |
| | ONE THAT MAY REQUIRE ASSISTANCE ONTO |
| | THE STAGE. THAT IT WILL BE READILLY |
| | AVAILABLE ON REQUEST. |
| | (B) LOCATE ON THE ARCHITECTS FLOOR PLAN |
| | THE LOCATION WHERE THE LIFT WILL BE |
| | USED AND INDICATE THE AREA IT WILL |
| | BE STORED AT WHEN NOT IN USE. |
| | (C) PROVIDE ADDITIONAL INFORMATION |
| | THE MANUFACTURES SPECIFICATIONS, |
| | WHAT TYPE OF DESIGN:ENTER/ EXIT OF |
| | LIFT, SYSTEMS DESCRIPTION OF PLAT- |
| | FORM, GUARDRAILS OR PANELS, DOORS |
| | OR GATES, DRIVE UNIT, CONTROLS, |
| | SIGNALS OR LIMIT SWITCHES, POWER |
| | REQUIRED, INDICATE ON THE FLOOR PLAN |
| | THE POWER SOURCE. |
| | (D) PROVIDE SHOP DRAWINGS OF THE SYSTEM |
| | WITH THE LOAD LIMITATIONS. IS THE |
| | SAFE LOAD NOT TO EXCEED INDICATED |
| | ON THE UNIT. |
| | (E) ASSUMING THIS IS A PORTABLE UNIT HOW |
| | IS THE TRANSITION FROM FINISH FLOOR |
| | TO THE VERTICAL LIFT MADE, WHAT IS |
| | THE SLOPE AND THE LENGTH OF THE RE- |
| | REQUIRED RAMP? HOW IS A SAFE TRANSI- |
| | TION MADE FROM THE VERTICAL LIFT |
| | WHILE IN USE TO THE STAGE? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |