2003-01-15 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.SUBMITTAL/INSTALLATION INSTRUCTIONS
 FOR THE FIRE WRAP. (FIRE WRAP ABOVE
 HOOD CEILING RATED CHASE TO BEGIN AT
 THE MEZZANINE LEVEL).
  
 2.PLAN SHEET M-2.04, PLAN INDICATES
 THE GREASE DUCT & SUPPLY DUCT ARE IN
 THE SAME SHAFT.AS PER NFPA 96 4-7.6,
 MULTIPLE DUCTS SHALL NOT BE PERMITTED IN
 A SINGLE ENCLOSURE. 2001 FBC(M) 506.3.12
 GREASE DUCT ENCLOSURE SHALL BE SEPARATED
 FROM THE DUCT A MINIMUM OF 6" AND A
 MAXIMUM OF 12" & SHALL SERVE A SINGLE
 GREASE EXHAUST DUCT SYSTEM.
  
 3.PLEASE NOTE AIR VELOCITY SHALL BE
 A MINIMUM OF 1,500 FPM & NOT GREATER
 THAN 2,500 FPM.2001 FBC(M) 506.3.6.
  
 4.PLANS SUBMITTED WITH BUILDING PERMIT
 INDICATE A HOOD FOR THE DISHWASHER.
 PLEASE PROVIDE SUBMITTAL FOR HOOD.
  
 PROVISO:WELDS TO BE INSPECTED PRIOR TO
 COVERING WITH WRAP OR INSTALLED IN SHAFT
  
 ADDITIONAL PERMIT REQUIRED FOR FIRE
 SUPRESSION.PROVIDE PLANS WITH PERMIT
 APPLICATION.
  