| Plan Review Notes For Permit 03010697 |
| Permit Number |
03010697 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-07 00:00:00 | PROVISO: | | | | | | AIR VELOCITY WITHIN THE DUCT SYSTEM | | | SHALL BE A MINIMUM OF 1,500 FPM & NOT | | | GREATER THAN 2,500 FPM. | | | | | | PROVIDE MANUFACTURERS INSTALLATION | | | INSTRUCTIONS FOR THE 3M FIREWRAP ON THE | | | JOBSITE AT TIME OF INSPECTION. | | | | | | WELDS ON DUCT SHALL BE INSPECTED PRIOR | | | TO COVERING. | | | | | | TEST & BALANCE REQUIRED FOR FINAL. | | | | | | ADDITIONAL PLANS & PERMIT REQUIRED FOR | | | FIRE SUPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|