Plan Review Notes
Plan Review Notes For Permit 03010610
Permit Number 03010610
Review Stop P
Sequence Number 2
Notes
Date Text
2003-06-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN. FIRST FLOOR BATH-
 ROOM HAS A W/C, A BIDET, A SHOWER, AND A
 LAV. RISER ONLY SHOWS W/C AND A LAV.
 FIRST FLOOR FLOOR PLAN DOES NOT SHOW A
 WASH MACHINE OR LAUNDRY SINK, BUT THEY
 ARE SHOWN ON THE RISER DIAGRAM. THE SEC-
 OND FLOOR BATHROOM SHOWS A W/C, A BIDET,
 A SHOWER, AND A LAV, BUT THE RISER DIA-
 GRAM SHOWS A W/C, A TUB, AND A LAV.
 RISER DIAGRAM SHALL REFLECT THE FLOOR
 PLAN. SHOW ONLY THOSE FIXTURES THAT WILL
 BE ADDED TO SYSTEM ON THE FIRST AND SEC-
 OND FLOORS.SHEET 3 OF 6
 2) SHEET 5 0F 6 SECOND SANITARY RISER
 DIARGAM DOES NOT REFLECT THE FLOOR PLAN.
 FIRST FLOOR PLAN SHOWS A BIDET IN BATH-
 ROOM AND RISER DOES NOT SHOW A BIDET.
 SECOND FLOOR PLAN SHOWS A BIDET BUT
 RISER DIAGRAM SHOWS 2 WATER CLOSETS.
 ALSO BOTH BATHROOMS HAVE DRY HORIZONTAL
 VENTS WHICH ARE NOT ALLOWED PER SECTION
 905.3.
 3) SECTION 104.2.1 AS REQUIRED BY SEC
 104.3.1.1 OF THE CODE, TWO OR MORE COP-
 IES OF SPECIFICATIONS, AND OF DRAWINGS
 DRAWN TO SCALE WITH SUFFICIENT CLARITY
 AND DETAIL TO INDICATE THE NATURE AND
 OF THE WORK, SHALL ACCOMPANY THE APPLI-
 CATION FOR A PERMIT.
 4) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692