| 2003-06-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1) SANITARY RISER DIAGRAM DOES NOT RE- |
| | FLECT THE FLOOR PLAN. FIRST FLOOR BATH- |
| | ROOM HAS A W/C, A BIDET, A SHOWER, AND A |
| | LAV. RISER ONLY SHOWS W/C AND A LAV. |
| | FIRST FLOOR FLOOR PLAN DOES NOT SHOW A |
| | WASH MACHINE OR LAUNDRY SINK, BUT THEY |
| | ARE SHOWN ON THE RISER DIAGRAM. THE SEC- |
| | OND FLOOR BATHROOM SHOWS A W/C, A BIDET, |
| | A SHOWER, AND A LAV, BUT THE RISER DIA- |
| | GRAM SHOWS A W/C, A TUB, AND A LAV. |
| | RISER DIAGRAM SHALL REFLECT THE FLOOR |
| | PLAN. SHOW ONLY THOSE FIXTURES THAT WILL |
| | BE ADDED TO SYSTEM ON THE FIRST AND SEC- |
| | OND FLOORS.SHEET 3 OF 6 |
| | 2) SHEET 5 0F 6 SECOND SANITARY RISER |
| | DIARGAM DOES NOT REFLECT THE FLOOR PLAN. |
| | FIRST FLOOR PLAN SHOWS A BIDET IN BATH- |
| | ROOM AND RISER DOES NOT SHOW A BIDET. |
| | SECOND FLOOR PLAN SHOWS A BIDET BUT |
| | RISER DIAGRAM SHOWS 2 WATER CLOSETS. |
| | ALSO BOTH BATHROOMS HAVE DRY HORIZONTAL |
| | VENTS WHICH ARE NOT ALLOWED PER SECTION |
| | 905.3. |
| | 3) SECTION 104.2.1 AS REQUIRED BY SEC |
| | 104.3.1.1 OF THE CODE, TWO OR MORE COP- |
| | IES OF SPECIFICATIONS, AND OF DRAWINGS |
| | DRAWN TO SCALE WITH SUFFICIENT CLARITY |
| | AND DETAIL TO INDICATE THE NATURE AND |
| | OF THE WORK, SHALL ACCOMPANY THE APPLI- |
| | CATION FOR A PERMIT. |
| | 4) SEE ATTACHED SHEET CONCERNING FLORIDA |
| | STATUTE 553.80(2)(B). |
| | |