| Plan Review Notes For Permit 03010610 |
| Permit Number |
03010610 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-07 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE FS/FAC, PLANS MUST | | | BE SIGNED AND SEALED BY THE ENGINEER OF | | | RECORD. 471.025. | | | | | | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE | | | AND LOAD CALCULATIONS, A/C LOAD SHOWS | | | ONLY SHOW ONE 10KW AHU AND PANEL SCHED- | | | -ULE SHOWS TWO. | | | | | | 3)NOTE: PLEASE LIST THE REQ`D BEDROOM | | | ARC FAULT CIRCUITS PER 210-12 | | | | | | 4)NOTE: IT IS NOTED ON RISER THAT METER | | | IS EXISTING? PLEASE SUBMIT AIC RATING | | | FOR NEW MCB PANEL. 110-9/215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|