2003-02-07 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE FS/FAC, PLANS MUST
 BE SIGNED AND SEALED BY THE ENGINEER OF
 RECORD. 471.025.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND LOAD CALCULATIONS, A/C LOAD SHOWS
 ONLY SHOW ONE 10KW AHU AND PANEL SCHED-
 -ULE SHOWS TWO.
  
 3)NOTE: PLEASE LIST THE REQ`D BEDROOM
 ARC FAULT CIRCUITS PER 210-12
  
 4)NOTE: IT IS NOTED ON RISER THAT METER
 IS EXISTING? PLEASE SUBMIT AIC RATING
 FOR NEW MCB PANEL. 110-9/215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  