| Date |
Text |
| 2003-03-06 00:00:00 | 1-DRAWINGS ARE STILL MISSING INFORMATION |
| | REQUIRED BY SEC. 1606.1.7 FBC 2001. |
| | SEE THIS SECTION FOR REQUIRED FIVE (5) |
| | ITEMS TO BE INCLUDED IN DRAWINGS. |
| | 2-CLARIFY WHAT ARE THE DESIGN WIND PRE- |
| | SSURES WRITTEN BY HAND ON THE SITE |
| | PLAN. ARE THESE FOR COMPONENT AND |
| | CLADDING?. PLEASE, REVISE ORIGINAL |
| | DRAWING. DON'T WRITE IT BY HAND. |
| | 3-CLARIFY WHY WINDOWS ON BEDROOMS 1 & 2 |
| | HAVE SAFETY GLASS?. SEC. 104.2.1.2 |
| | CITY AMEMDMENTS TO FBC 2001. |
| | 4-DIMENSIONS GIVEN ON SITE PLAN DON'T |
| | ADD UP CORRECTLY. REVISE AS REQUIRED. |
| | 5-PROVIDE DETAIL/SPECS FOR CEILING INS- |
| | TALLATION AT FRONT AND REAR PORCH. |
| | CLEARLY SPECIFY FASTENERS AND SPACING |
| | AS REQ'D BY ASTM C926 AND ASTM C1063. |
| | SECTION 2504.2 FBC 2001. |
| | 6-STORM SHUTTERS INFORMATION SUBMITTED: |
| | A)DRAWINGS DON'T MATCH PRODUCT APPROVAL. |
| | |
| | 7-IMPACT FEES: NEED DRAWINGS STAMPED BY |
| | PALM BEACH COUNTY SHOWING EITHER NO |
| | FEES DUE OR CREDIT FOR EXISTING HOUSE. |
| | 8-NEED PRODUCT APPROVAL FOR ENTRY DOOR |
| | W/ GLASS. SEE EXTERIOR ELEVATIONS. |
| | **NOTE: CLARIFY WHY ENTRY DOOR HAVE NOT |
| | STORM SHUTTERS IF IT HAS GLASS?SEE |
| | EXTERIOR ELEVATIONS. |
| | 9-REVISE STRUCTURAL BUCK DETAIL. SEE |
| | SECTION 1707.4.4 FBC 2001 FOR SPECIFIC |
| | REQUIREMENTS FOR 2X BUCK AND REVISE |
| | DETAIL ACCORDINGLY. ALSO, DRAW DETAIL |
| | AT A LARGER SCALE TO BE ABLE TO SEE |
| | BUCK LOCATION. |