| 2003-01-17 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE NOTE THE FOLLOWING,MAKE |
| | CORRECTIONS,AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | ELECTRICAL CONTRACTOR TO PROVIDE SAME |
| | WHEN APPLYING FOR A PERMIT. |
| | |
| | 2} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 4} THE GROUNDING ELECTRODE SYSTEM MUST |
| | COMPLY WITH 250-50(A)(B)&(C),CWP IF |
| | AVAILABLE. |
| | |
| | 5} PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE PER 210-12. |
| | |
| | 6} NOTE ALL KITCHEN COUNTERTOP |
| | RECEPTACLES SHALL BE GFCI'S PER |
| | 210-8(A)(6). |
| | |
| | 7} PROVIDE AN OUTLET FOR THE A/C |
| | EQUIPMENT PER210-63. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |