| | BUILDING PLAN REVIEW |
| | PERMIT: 03010589 |
| | ADD: ONE N CLEMATIS SUITE 100 |
| | CONT: QUALITY CONCRETE |
| | TEL: (954)444-4435 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 2) 1606.1.1 BUILDINGS > 60' ARE TO BE DE |
| | SIGNED TO ASCE 7-98, BIFOLD DOORS ARE IN |
| | AN "END ZONE" INDICATE POSITIVE AND |
| | NEGITIVE WIND PRESSURES. |
| | |
| | 3) MISSING THE NON-IMPACT PRODUCT APPROV |
| | AL FROM ARCH ALUM. NOTE PRODUCT TESTING |
| | REPORT WILL INDICATE AS TO WHAT CONFIG- |
| | URATION THE DOORS WERE TESTED IN, IF |
| | THEY WERE NOT TESTED IN A BIFOLD MANNER. |
| | INDICATE HOW DOORS ARE HINGED, CONTIN- |
| | IOUS? IF HINGES HOW MANY WHAT SIZE, IS |
| | THE DOOR AND FRAME WOOD OR METAL? |
| | |
| | 4)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. |
| | |
| | 5) PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 6)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | BUILDING PLAN REVIEW |