| Plan Review Notes For Permit 03010589 |
| Permit Number |
03010589 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) SHT MEP1.1 SANITARY RISER DIAGRAM, | | | DISHWASHER SHALL DRAIN INTO SANITARY. | | | 2) SHT MEP1.0 GAS RISER DIAGRAM, PIPE | | | SIZE FOR LINE WITH EMERGENCY SOLENOID | | | VALVE NOT SIZED PROPERLY. MINIMUM 2" | | | PIPE REQUIRED PER TABLE 402(2). (586K) | | | @ 110' | | | 3) SHT MEP1.0 GAS RISER NOTES, CODE IN | | | USE IS FBC-2001 FUEL GAS. TABLE 402(2), | | | NOTE #1. NOTE #3 SHALL READ FBC-2001 | | | FUEL GAS AND SECTION 409. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|