| Plan Review Notes For Permit 03010452 |
| Permit Number |
03010452 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-28 00:00:00 | *********** UNSAT ******************** | | | | | | 1)NOTE: PLEASE REMOVE SD FROM KITCHEN | | | AREA. NOT PERMITTED PER NFPA-72 8-1.4.1. | | | 6. | | | | | | 2)NOTE: PLEASE NOTE, MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | | APNEL "B". SIZE PER 250-122 | | | | | | 3)NOTE: PLEASE SEE MIN SIZING OF GROUND- | | | -ING ELECTRODE CONDUCTOR PER 250-66. | | | PLEASE ALSO SEE MIN SIZE OF SERVICE | | | CONDUCTORS FOR 400A SERVICE ON 310-15 | | | FOR SIZING GROUNDING ELECTRODE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWYE PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|