| Notes |
| Date |
Text |
| 2003-03-10 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING CHANGES TO | | | PLANS PRIOR TO ROUGH | | | INSPECTION,RESUBMIT FOR REVIEW. | | | | | | 1} THE LAUNDRY CIRCUIT ON THE PANEL | | | SCHEDULE SHOULD BE CALCULATED @ 1500 | | | VA.PER210-16(B). | | | | | | 2} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.ON PANEL | | | SCHEDULE. | | | | | | 3} THE GROUNDED ELECTRODE CONDUCTOR IS | | | TOO SMALL FOR 400 AMP SERVICE,SEE | | | 250-66.SHOULD BE 1/0. | | | | | | 4} THE FEEDER TO TO PANEL "B" SHOULD | | | CONTAIN AN EQUIPMENT GROUND PER 250-122. | | | | | | 5} THE SMOKE DETECTOR IN THE KITCHEN | | | DOES NOT COMPLY WITH 8-1.4.2 | | | NFPA-72,SHOULD BE CHANGED TO A HEAT | | | DETECTOR OR BE REMOVED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT 8392 |
|