| Plan Review Notes For Permit 03010450 |
| Permit Number |
03010450 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-18 00:00:00 | DENIED; | | | PAGE A-1 PLUMBING RISER; | | | 1.ONLY FIXTURES IN THE BATHROOM GROUP | | | SHALL CONNECT TO THE WET VENTED | | | HORIZONTAL BRANCH DRAIN. SEC.909.1. | | | 2ND FL. LAUNDRY AND MASTER BATH. | | | 2.TABLE 909.3 | | | ONLY 4 FU'S ON 2" WET VENT. | | | 3.MASTER BATH FLOOR PLAN SHOWS 2 LAVS. | | | RISER DIAGRAM SHOWS 3. | | | 4.RISER DIAGRAM SHOWS SINK ON 2ND FLOOR | | | NOT SHOWN ON FLOOR PLAN. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|