| 2003-03-24 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 2/11/03: |
| | |
| | 2) SUBMITTAL OF THE RECEIPT FOR IMPACT |
| | FEES IS NOTED BUT THE SUBMITTED PLANS |
| | ARE NOT STAMPED BY PAIM BEACH COUNTY |
| | BUILDING DEPT TO VERIFY THAT THEY ARE |
| | THE PLANS ASSESSED FOR IMPACT.INSERT |
| | ONE STAMPED PLAN SHEET INTO EACH SET. |
| | |
| | 7) FBC* 104.2.1CANTILEVERED CONCRETE |
| | EYEBROW DETAIL 5/S4.4.THE SUBMITTED |
| | HAND-DRAWN SKETCH DOES NOT SHOW THE |
| | DOWEL BAR BEING USED IN ACCORDANCE WITH |
| | THE MANUFACTURER'S RECOMMENDATIONS. |
| | REVIEW AND AMEND THE DETAIL AS NECESSARY |
| | THE DETAILS SHALL BEAR THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | SPECIFYING THE DOWEL CONNECTORS.THE |
| | DETAILS SHALL THEN BE SIGNED AND DATED |
| | BY THE ENGINEER OF RECORD TO CONFIRM |
| | THAT THEY HAVE BEEN REVIEWED AND |
| | ACCEPTED. |
| | |
| | 13)FBC 13-101.1.6SHELL BUILDINGS. |
| | THE PROJECT INFORMATION HAS NOT BEEN |
| | ENTERED ON PAGE 1 OF THE SUBMITTED CODE |
| | COMPLIANCE FORM 400B.ALSO, FOR SHELL |
| | BUILDINGS, ALL ASSUMPTIONS MADE ABOUT |
| | FEATURES NOT INSTALLED UNTIL LATER, AND |
| | ARE NOT ON THE BUILDING PLANS, SHALL BE |
| | LISTED AND APPENDED TO FORM 400B.THIS |
| | WILL BE COMPARED TO THOSE FEATURES |
| | PROPOSED FOR INSTALLATION AT A LATER |
| | DATE WHEN COMPLETION OF THE BUILDING IS |
| | PERMITTED. |
| | |
| | 15) DOOR AND WINDOW SCHEDULES, SHEETS |
| | A-5 AND A-7 SHOW A 9'-0" HIGH STOREFRONT |
| | DOOR WHICH EXCEEDS THE MAXIMUM HEIGHT |
| | COVERED BY SUBMITTED PRODUCT APPROVAL |
| | NOA# 01-0919.02 |
| | |
| | 16) FBC* 105.3RESIDENT INSPECTOR |
| | PROGRAM.SUBMIT A THIRD SET OF THE |
| | PLANS. |