| Plan Review Notes For Permit 03010432 |
| Permit Number |
03010432 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHTS A-6, A-9, & A-15 DETAIL #3. | | | A-6 SHOWS SCUPPER SIZE TO BE 12"X20", | | | A-9 SHOWS SCUPPER SIZE TO BE 10"X23", | | | A-15 SHOWS SCUPPER SIZE TO BE 12"X20", | | | PLEASE CLAIRFY. | | | 2) PLEASE PROVIDE CALCULATIONS FOR ROOF | | | DRAINS, PRIMARY AND SECONDARY PER SEC | | | 1106, AND 1107. SHOW TOTAL SQ FT INCLUD- | | | ING 1/2 AREA OF ALL VERTICAL WALLS & | | | PARAPET WALLS. | | | 3) SHT PO.1 WATER RISER, AIR CHAMBERS | | | ARE NOT APPROVED AND WATER HAMMER ARRES- | | | TORS REQUIRED BY 604.9 SHALL BE LOCATED | | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | | NOT ABOVE THE CEILING AT THE TOP OF THE | | | DROPS. | | | 4) SHT PO-1 PLUMBING NOTES #13 AIR CHAM- | | | BERS ARE NOT APPROVED. PLEASE DELETE | | | FROM REFERENCE. | | | 5) SHT P2.1 FLOOR DRAIN FROM PUMP ROOM | | | SHALL DRAIN TO SANITARY NOT STORM. | | | 6) SEPARATE IRRIGATION PLANS AND PERMIT | | | REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|