| Plan Review Notes For Permit 03010432 |
| Permit Number |
03010432 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-07 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM, | | | PLEASE SHOW SIZE OF METER AND MAIL DISC | | | FEEDING NEW PANEL 1HP. PLEASE ALSO | | | SEE LOAD SHOWN AT 147A'S WITH #3'S | | | FEEDING A 225A PANEL? PLEASE SIZE | | | CONDUCTORS ACCORDING TO 310-16 AND OCP | | | PER 240. | | | | | | 2)NOTE: PLEASE SHOW AIC RATING OF THAT | | | SAME NEW (HOUSE) DISCONNECT. | | | IF DIFFERENT FROM TYPICALS?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|