2003-02-07 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM,
 PLEASE SHOW SIZE OF METER AND MAIL DISC
 FEEDING NEW PANEL 1HP. PLEASE ALSO
 SEE LOAD SHOWN AT 147A'S WITH #3'S
 FEEDING A 225A PANEL? PLEASE SIZE
 CONDUCTORS ACCORDING TO 310-16 AND OCP
 PER 240.
  
 2)NOTE: PLEASE SHOW AIC RATING OF THAT
 SAME NEW (HOUSE) DISCONNECT.
 IF DIFFERENT FROM TYPICALS??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372