| 2003-02-11 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT SHALL BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | A COPY OF THE RECEIPT SUBMITTED, TO CITY |
| | OF WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC 705.1.1.2NORTH END OF THE WEST |
| | ELEVATION.THAT SECTION OF THE WALL |
| | WHICH IS WITHIN 15 FEET OF THE PROPERTY |
| | LINE SHALL HAVE ALL OPENINGS EQUIPPED |
| | WITH APPROVED OPENING PROTECTIVES (SEE |
| | FBC 705.1.3) WITH A RATING OF NOT LESS |
| | THAN 3/4 HOUR. |
| | |
| | 4) FBC* 1804.2.2SUBMIT A GEOTECHNICAL |
| | REPORT (REF: DRAWING SHEET S5.2, |
| | SITE WORK NOTE #2). |
| | |
| | 5) FBC* 104.2.1.2FOUNDATION SECTION |
| | 7/S4.1 (TYP).NO ANCHORAGE |
| | REINFORCEMENT IS SHOWN BETWEEN THE TILT- |
| | UP WALL PANELS AND THE FOUNDATIONS. |
| | SUBMIT AN ENGINEER'S SIGNED AND SEALED |
| | LETTER, CONFIRMING THAT NO ANCHORAGE TO |
| | THE FOUNDATION IS REQUIRED FOR UPLIFT OR |
| | FOR LATERAL LOAD DUE TO THE RETAINED |
| | FILL AND THE WAREHOUSE FLOOR SURCHARGE |
| | LOADS. |
| | |
| | 6) NOTE:DETAIL 8/S4.1 HAS BEEN RED- |
| | LINED TO REFERENCE 9/S4.1 WHICH DOES NOT |
| | APPEAR TO BE CALLED UP ANYWHERE ON THE |
| | PLANS. |
| | |
| | 7) PROVISO: FBC* 104.2.1.2 DETAIL 5/S4.4 |
| | INCIDENTAL/MAINTENANCE LOADING ON THE |
| | CANTILEVER CONCRETE 'EYEBROW'.SUBMIT |
| | SHOP DRAWINGS OF THE MEANS OF ATTACHING |
| | THE 'EYEBROW' TO THE TILT-UP WALL PANEL. |
| | |
| | 8) FBC* F102.2.4FIRE DISTRICT.AMEND |
| | THE PLANS TO INCLUDE THE REQUIREMENT FOR |
| | THE ROOF COVERING TO BE CLASS A OR B, AS |
| | THE BUILDING IS WITHIN THE FIRE DISTRICT |
| | |
| | 9) SUBMIT A PRODUCT APPROVAL FOR THE |
| | PROPOSED ROOFING SYSTEM. |
| | |
| | 10) SUBMIT A PRODUCT APPROVAL FOR THE |
| | PROPOSED HURRICANE MISSILE IMPACT |
| | PROTECTION SHUTTERS. |
| | |
| | 11) METAL AWNINGS.SUBMIT DETAILS, OR |
| | A SEPARATE AWNING PERMIT APPLICATION |
| | WILL BE REQUIRED. |
| | |
| | 12) A SEPARATE PERMIT APPLICATION WILL |
| | BE REQUIRED FOR THE DUMPSTER ENCLOSURE. |
| | |
| | 13) NOTE:FBC 13-101.1.6ENERGY CODE |
| | COMPLIANCE SHALL BE DEMONSTRATED BY |
| | SUBMITTAL OF CODE COMPLIANCE FORM 400B |
| | WITH A LIST APPENDED TO DESCRIBE THE |
| | ASSUMPTIONS MADE ABOUT BUILDING FEATURES |
| | NOT INSTALLED DURING THIS PHASE OF THE |
| | PROJECT. |
| | |
| | 14) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |