| Plan Review Notes For Permit 03010378 |
| Permit Number |
03010378 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-21 00:00:00 | | | | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) PLEASE PROVIDE A SANITARY RISER DIA- | | | GRAM AND A WATER RISER DIAGRAM. SECTION | | | 104.2 AND SECTION 104.3.1.1 | | | 2) SHT P-1 WATER HEATER DETAIL AND NOTE | | | BY W/HEATER ON FLOOR PLAN, FLOOR DRAINS | | | ARE NOT AN APPROVED INDIRECT WASTE REC- | | | EPTOR. PLEASE PROVIDE A FLOOR SINK FOR | | | RELIEF VALVE OR DRAIN INTO MOP SINK WITH | | | AN AIR GAP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|