| Plan Review Notes For Permit 03010378 |
| Permit Number |
03010378 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-24 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLANS ARE SHOWING ALL WORK TO BE | | | UNDER 2000 NEC. PLEASE NOTE, WE ARE | | | UNDER THE 99NEC.FYI, THE NEXT NEC AFTER | | | THAT WOULD BE 2002. | | | | | | | | | 2)NOTE: PLEASE CLARIFY LOADS BEING BEING | | | ADDED AND EXISTING LOADS. PLEASE NOTE | | | A LOAD CALCULATION IS REQ`D FOR LOADS | | | BEING ADDED DUE TO AGE OF PANELS AND/OR | | | SERVICE IN EXISTING BLDG.215-5 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|