Date Text
2003-05-29 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE NECESSARY CHANGES FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 2} PLEASE SEE ARTICLE 230-70 WEST PALM
 BEACH AMMENDMENTS,TO DETERMINE IF A
 DISCONNECT IS REQUIRED AT THE METER.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR
 FROM PANEL "B" TO GROUND PARALLELS THE
 GROUNDED NEUTRAL AND MAY NOT BE
 INSTALLED.
  
 4} THE FEED FROM PANEL "C" TO "B" IS
 SHOWN AS #3/0 ON THE RISER & #1/0 ON
 THE PANEL SCHEDULE. PLEASE CLARIFY.
  
 5} PLEASE NOTE THAT CKT. BREAKERS #41 &
 42 APPEAR TO HAVE THE GRONDING CONDUCTOR
 ATTACHED TO THEM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  