| Plan Review Notes For Permit 03010347 |
| Permit Number |
03010347 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-29 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE NECESSARY CHANGES FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | 2} PLEASE SEE ARTICLE 230-70 WEST PALM | | | BEACH AMMENDMENTS,TO DETERMINE IF A | | | DISCONNECT IS REQUIRED AT THE METER. | | | | | | 3} THE GROUNDING ELECTRODE CONDUCTOR | | | FROM PANEL "B" TO GROUND PARALLELS THE | | | GROUNDED NEUTRAL AND MAY NOT BE | | | INSTALLED. | | | | | | 4} THE FEED FROM PANEL "C" TO "B" IS | | | SHOWN AS #3/0 ON THE RISER & #1/0 ON | | | THE PANEL SCHEDULE. PLEASE CLARIFY. | | | | | | 5} PLEASE NOTE THAT CKT. BREAKERS #41 & | | | 42 APPEAR TO HAVE THE GRONDING CONDUCTOR | | | ATTACHED TO THEM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|