2003-03-26 00:00:00PROVISO:
  
 AHU #1 & 2, SHALL COMPLY WITH 2001 FBC,
 (MECH) 306.3, THE CLEAR ACCESS OPENING
 DIMENSIONS SHALL BE A MINIMUM OF 20" X
 30".
  
 AHU #1 & 2 SHALL ALSO COMPLY WITH 2001
 FBC CHAPTER 13 SECTION 610.1.ABC.3.5.2.
  
 PROVIDE FLOAT SWITCH OR SECONDARY DRAIN
 LINE TERMINATING AT A CONSPICUOUS POINT
 REQUIRED ON THE AUXILIARY DRAIN PANS.
  