| Notes |
| Date |
Text |
| 2003-03-26 00:00:00 | PROVISO: | | | | | | AHU #1 & 2, SHALL COMPLY WITH 2001 FBC, | | | (MECH) 306.3, THE CLEAR ACCESS OPENING | | | DIMENSIONS SHALL BE A MINIMUM OF 20" X | | | 30". | | | | | | AHU #1 & 2 SHALL ALSO COMPLY WITH 2001 | | | FBC CHAPTER 13 SECTION 610.1.ABC.3.5.2. | | | | | | PROVIDE FLOAT SWITCH OR SECONDARY DRAIN | | | LINE TERMINATING AT A CONSPICUOUS POINT | | | REQUIRED ON THE AUXILIARY DRAIN PANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|