| 2003-03-19 00:00:00 | ************ UNSAT ****************** |
| | |
| | PLANS NEED TO PLACED INTO TWO SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | 1)NOTE: PLEASE SHOW GARAGE RECEPTS AS |
| | GFI. 210-8 |
| | |
| | 2)NOTE: PLEASE SHOW MAIN GROUNDING |
| | ELECTRODE CONDUCTOR TO FOOTER STEEL AS |
| | 1/0. PLEASE NOTE, SHOWN TO SUPPLEMENTAL |
| | AND THEN A #6 TO FOOTER STEEL. PLEASE |
| | CHANGE. |
| | 250-50 |
| | |
| | 3)NOTE: PLEASE CLARIFY TWO SD`S SHOWN |
| | IN GARAGE W/IN ABOUT 4' OF EACH OTHER?? |
| | |
| | 4)NOTE: PLEASE SEE MISSING SD INSIDE |
| | BEDROOM. PER NFPA-72 8-1.4.2 |
| | |
| | 5)NOTE: PLEASE SEE MISSING CONTROL OF |
| | EGRESS LIGHTING LEAVING FIRST FLOOR |
| | ENTRY TO REAR STOOP, AND ALSO 2ND FLR |
| | LEAVING TO BRIDGE AREA. 210-70 |
| | |
| | 6)NOTE: PLEASE SUBMIT A PANEL SCHEDULE |
| | FOR ALL NEW CIRCUITING. PLEASE SUBMIT |
| | LOAD CALCULATIONS W/ NEW AND EXISTING |
| | LOADS. PLEASE SHOW OCP AND WIRE SIZES IN |
| | PANEL. |
| | |
| | 7)NOTE: PLEASE LIST THE REQ`D DEDICATED |
| | BATH CIRCUIT(S) AS #12/20 210-52D/210-11 |
| | -C-3. |
| | |
| | 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | CIRCUITS PER 210-12 |
| | |
| | 9)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR BETWEEN MAIN PANEL |
| | AND SUB-PANEL. SIZE PER 250-122 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |