Plan Review Notes
Plan Review Notes For Permit 03010347
Permit Number 03010347
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-19 00:00:00************ UNSAT ******************
  
 PLANS NEED TO PLACED INTO TWO SETS FOR
 REVIEW AND STAMPING.
  
 1)NOTE: PLEASE SHOW GARAGE RECEPTS AS
 GFI. 210-8
  
 2)NOTE: PLEASE SHOW MAIN GROUNDING
 ELECTRODE CONDUCTOR TO FOOTER STEEL AS
 1/0. PLEASE NOTE, SHOWN TO SUPPLEMENTAL
 AND THEN A #6 TO FOOTER STEEL. PLEASE
 CHANGE.
 250-50
  
 3)NOTE: PLEASE CLARIFY TWO SD`S SHOWN
 IN GARAGE W/IN ABOUT 4' OF EACH OTHER??
  
 4)NOTE: PLEASE SEE MISSING SD INSIDE
 BEDROOM. PER NFPA-72 8-1.4.2
  
 5)NOTE: PLEASE SEE MISSING CONTROL OF
 EGRESS LIGHTING LEAVING FIRST FLOOR
 ENTRY TO REAR STOOP, AND ALSO 2ND FLR
 LEAVING TO BRIDGE AREA. 210-70
  
 6)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 FOR ALL NEW CIRCUITING. PLEASE SUBMIT
 LOAD CALCULATIONS W/ NEW AND EXISTING
 LOADS. PLEASE SHOW OCP AND WIRE SIZES IN
 PANEL.
  
 7)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT(S) AS #12/20 210-52D/210-11
 -C-3.
  
 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS PER 210-12
  
 9)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN PANEL
 AND SUB-PANEL. SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372