| 2003-03-27 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PAY IMPACT FEES TO PALM BEACH COUNTY |
| | BRING BACK STAMPED DRAWINGS AND PAID |
| | RECEIPT. |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-PROVIDE SOIL TEST REPORT. |
| | 4-PROVIDE ALL INFORMATION (5 ITEMS ) AS |
| | REQUESTED ON SEC. 1606.1.7 FBC 2001. |
| | INCLUDING INTERNAL DESIGN PRESSURES |
| | AND COMPONENTS AND CLADDING. |
| | 5-ALL DRAWINGS THAT ARE REPLACED NEED TO |
| | BE RE-STAMPED BY HISTORICAL PRIOR TO |
| | SUBMITTAL TO THIS OFFICE. |
| | NOTE: ONLY TWO SETS OF DRAWINGS ARE |
| | REQUIRED, NOT THREE. |
| | 6-PROVIDE COMPLETE GUARDRAIL & HANDRAILS |
| | DETAILS. SEE SEC. 1608.2 FOR DESIGN |
| | CRITERIA. ALSO, SEE SEC. 1007.5 AND |
| | SEC. 1015 FBC 2001. |
| | 7-CLARIFY AREA TABULATION ON SHEET A-4: |
| | CLEARLY IDENTIFY GARAGE AREA AND |
| | VESTIBULE GROUND FLOOR AREA. CLARIFY |
| | WHAT'S VESTIBULE GROUND FLOOR AREA? |
| | INCLUDE THIS AREA ON ENTRY HALL AND |
| | CLOSET AREA. |
| | 8-PROVIDE COMPLETE DETAIL FOR 2X BUCK |
| | DETAIL. SEE SEC. 1707.4.4.2 FBC 2001 |
| | FOR APPROPRIATE INSTALLATION OF 2X |
| | STRUCTURAL BUCK TO SUBSTRATE. |
| | 9-PROVIDE 2 COPIES OF PRODUCT APPROVALS |
| | FOR DOORS AND WINDOWS ASSEMBLIES WITH |
| | TRANSOM ABOVE OR SIDELITES AS SINGLE |
| | ASSEMBLIES AS SHOWN ON PLANS. |
| | 10-PROVIDE 2 COPIES OF PRODUCT APPROVALS |
| | FOR STRUCTURAL DOOR & WINDOW MULLIONS |
| | 11-PROVIDE 2 COPIES OF PRODUCT APPROVAL |
| | FOR ROOF TILE. |