| Plan Review Notes For Permit 03010326 |
| Permit Number |
03010326 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-09 00:00:00 | ************ UNSAT ********** | | | | | | 1)NOTE: PLEASE CLARIFY LOAD SUMMARY AND | | | PANEL SCHEDULE SHOWING TWO DIIFERENT | | | KVA LOADS? PLEASE SHOW CONTINUOUS LOADS | | | AT 125%. | | | | | | 2)NOTE: PLEASE CLARIFY MISSING FEEDERS | | | FOR NEW PANEL?PLEASE | | | SIZE PER 310-16. | | | | | | 3)NOTE: PLEASE CLARIFY METHOD OF EQUIP- | | | -MENT GROUND BETWEEN MAIN DISC/METER | | | AND NEW PANEL "LL"> PLEASE NOTE, IF | | | NMC, PLEASE SIZE PER 250-122. | | | | | | 4)NOTE: PLEASE CLARFIY IF THERE IS NEW | | | OR EXISTING SIGN CIRCUIT PER 600-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|