| Plan Review Notes For Permit 02121457 |
| Permit Number |
02121457 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-11 00:00:00 | ********** NOTE **************** | | | | | | PLEASE SEE THE FOLLOWING IS A GIVEN | | | EXPLANATION FOR SYSTEM REQUESTED TO BE | | | INSTALLED AT "ESPLANADE GRANDE" | | | | | | 1)NOTE: PLEASE SEE THAT THE PROPOSED | | | LIGHTNING PROTECTION SYSTEM HAS BEEN | | | RESERCHED. WE HAVE NOT BEEN ABLE TO FIND | | | SUFFICIENT INFORMATION FOR THE SYSTEM TO | | | BE PERMITTED TO BE INSTALLED. | | | THE SYSTEM IS NOT RECOGNIZED BY NFPA 780 | | | | | | 2)NOTE: PLEASE NOTE, SYSTEM SEEMS TO | | | CONTAIN ALL LISTED PRODUCTS BUT SYSTEM | | | IS NOT A LISTED ASSEMBLY PER NFPA 70 | | | | | | PLEASE NOTE, AN OPTION THAT MAY BE TAKEN | | | AND WILL BE ACCEPTABLE BY THIS OFFICE, | | | IS TO HAVE A UL FIELD REPRESENTIVE DO AN | | | INSPECTION ON SYSTEM AND CERTIFY WITH | | | FIELD STICKERS AND A FOLLOW UP LETTER | | | TO KEEP AS RECORD. | | | | | | PLEASE CALL IF THERE ARE ANY QUESTIONS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|