Date Text
2003-03-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02121450
 ADD: 5820 N JOG RD
 CONT: ADVANCED ROOFING
 TEL: (954)868-0063
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION: UNKNOWN
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 REVISIONS ARE TO BE DESIGNATED WITH
 CLOUDS, DELTAS ETC...
  
 2) SHEET S-14 DESIGN CRITERIA,
 AS PER MEETING WITH THE ENGINEERS BEFORE
 THE ISSUANCE OF PLANS, PLANS WERE RED
 LINED TO RELFECT THE BUILDING DESIGN WAS
 DESIGNED TO THE 1997 SBC/ @ 110 MPH.
 TO USE THE 2001 FLORIDA BLDG CODE @ 140
 MPH THE ORIGINAL STEEL STRUCTURE WOULD
 REQUIRE CERTIFYING IT AT 140MPH, W/ AND
 IMPORTANCE FACTOR OF 1. THE ENGINEERS
 STATED THIS BUILDING WOULD NOT MAKE THE
 MORE STRIGENT WINDLOADING OF THE NEW
 CODE. THE COMPOST BUILDING CAN ASSUME AN
 IMPORTANCE FACTOR OF .77 (TABLE 1606,
 FOOTNOTE-A). 140X.77=107.8 WHICH IS
 BELOW THE 110 MPH WITHOUT CONVERTING
 FROM FASTEST 3 SECOND GUST TO FASTEST
 MILE (TABLE 1606.1.6.1), 107.8 /3 SEC
 GUST CONVERTS TO 87 MPH FASTEST MILE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412