Plan Review Notes
Plan Review Notes For Permit 02121272
Permit Number 02121272
Review Stop P
Sequence Number 2
Notes
Date Text
2003-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SHTS A.29, A.30, A.32, A.33, A.34,
 A.35, A.36, A.37, A.38, A.39, A.40, A.41
 A.42, A.43, A.44. & A.44A - PLEASE INDI-
 CATE SPECIFICATION "A" OR "B" PER RE-
 QUIREMENT 7B FHA-DESIGN MANUAL.
 2) SAME SHTS AS COMMENT #1, PLEASE IN-
 DICATE SIZE OF OPENING FOR W/C. MINIMUM
 OF 33" REQUIRED. (18 - 15).
 3) SHTS A.37 & A.38 IF THERE IS BOTH A
 BATHROOM AND A POWDER ROOM THEN THE
 BATHROOM WOULD BE REQURED TO BE USEABLE
 AND MEET REQUIREMENTS.
 4) SHT A.45 FACILITIES FOR POOL CABANA
 TO BE APPROVED AND STAMPED BY THE HEALTH
 DEPT. 901 EVERNIA ST. (FROM PREV. REVIEW
 5) SHT A.51 PROVIDE BACKING DETAIL THAT
 COMPLYS WITH FHA-DESIGN MANUAL REQUIRE-
 MENT 6.
 6) SHT P2.23 WATER HEATER DETAIL, PRESS-
 URE RELIEF VALVES SHALL NOT BE USED AS A
 MEANS FOR CONTROLLING THERMAL EXPANSION.
 SEE SECTION 504.5. AN EXPANSION TANK IS
 REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377