| Plan Review Notes For Permit 02121272 |
| Permit Number |
02121272 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | | | | 1) SHTS A.29, A.30, A.32, A.33, A.34, | | | A.35, A.36, A.37, A.38, A.39, A.40, A.41 | | | A.42, A.43, A.44. & A.44A - PLEASE INDI- | | | CATE SPECIFICATION "A" OR "B" PER RE- | | | QUIREMENT 7B FHA-DESIGN MANUAL. | | | 2) SAME SHTS AS COMMENT #1, PLEASE IN- | | | DICATE SIZE OF OPENING FOR W/C. MINIMUM | | | OF 33" REQUIRED. (18 - 15). | | | 3) SHTS A.37 & A.38 IF THERE IS BOTH A | | | BATHROOM AND A POWDER ROOM THEN THE | | | BATHROOM WOULD BE REQURED TO BE USEABLE | | | AND MEET REQUIREMENTS. | | | 4) SHT A.45 FACILITIES FOR POOL CABANA | | | TO BE APPROVED AND STAMPED BY THE HEALTH | | | DEPT. 901 EVERNIA ST. (FROM PREV. REVIEW | | | 5) SHT A.51 PROVIDE BACKING DETAIL THAT | | | COMPLYS WITH FHA-DESIGN MANUAL REQUIRE- | | | MENT 6. | | | 6) SHT P2.23 WATER HEATER DETAIL, PRESS- | | | URE RELIEF VALVES SHALL NOT BE USED AS A | | | MEANS FOR CONTROLLING THERMAL EXPANSION. | | | SEE SECTION 504.5. AN EXPANSION TANK IS | | | REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|