| 2003-03-18 00:00:00 | DENIED: |
| | |
| | COMMENT #2 FROM PREVIOUS REVIEW WAS NOT |
| | ADDRESSED: |
| | MASTER BATHROOMS TO ALL UNITS INDICATE |
| | AN EXHAUST FAN ONLY IN THE "TOILET" ROOM |
| | ONE WILL ALSO BE REQUIRED WHERE THE |
| | SHOWER, BATHTUB AND SINKS ARE LOCATED |
| | AS PER 2001 FBC(M) 402.3.1. |
| | |
| | DEVELOPED LENGTH FOR THE DRYER EXHAUST |
| | SHALL NOT EXCEED 25 FT AS PER 2001 |
| | FBC(M) 504.6.THERE IS A 5 FT REDUCTION |
| | FOR EACH 90 DEGREE RAD & 2 1/2 FT |
| | REDUCTION FOR EACH 45 DEGREE RAD. |
| | |
| | PLEASE NOTE UNITS 20,11,12,14,15,17,18, |
| | 21,23,24,26,27, & 28, 10" X 10" DROP |
| | DOWN FROM SECOND FLOOR INTO GARAGE AREA |
| | THEN BACK INTO THE FIRST FLOOR.THIS IS |
| | A RATED WALL & FLOOR ASSEMBLY.DUCT |
| | CANNOT EXCEED 100 SQ IN AND SHALL COMPLY |
| | WITH ALL OF 2001 FBC(M) 607.1.3 #3 ITEMS |
| | 1 THRU 4.WHERE THE 8" DUCT PENETRATES |
| | FROM THE GARAGE INTO THE "FOYER" THIS |
| | DUCT SHALL ALSO COMPLY WITH THE AFORE- |
| | MENTIONED CODE. |
| | |
| | DRYER EXHAUST WAS NOT ADDRESSED.MAX |
| | DEVELOPED LENGTH OF 25 FT WITH A 5 FT |
| | REDUCTION FOR EACH 90 DEGREE RAD & |
| | 2 1/2 FT REDUCTION FOR EACH 45 DEGREE |
| | RAD. |
| | |
| | PLEASE CLARIFY PLAN SHEET AC-2.28, POOL |
| | CABANA FLOOR PLAN - DETAIL INDICATES THE |
| | CONDENSING UNIT UPSTAIRS, THE ARCH PLAN |
| | SHEET A.45.01 INDICATES THIS TO BE THE |
| | AHU. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |