2003-03-18 00:00:00DENIED:
  
 COMMENT #2 FROM PREVIOUS REVIEW WAS NOT
 ADDRESSED:
 MASTER BATHROOMS TO ALL UNITS INDICATE
 AN EXHAUST FAN ONLY IN THE "TOILET" ROOM
 ONE WILL ALSO BE REQUIRED WHERE THE
 SHOWER, BATHTUB AND SINKS ARE LOCATED
 AS PER 2001 FBC(M) 402.3.1.
  
 DEVELOPED LENGTH FOR THE DRYER EXHAUST
 SHALL NOT EXCEED 25 FT AS PER 2001
 FBC(M) 504.6.THERE IS A 5 FT REDUCTION
 FOR EACH 90 DEGREE RAD & 2 1/2 FT
 REDUCTION FOR EACH 45 DEGREE RAD.
  
 PLEASE NOTE UNITS 20,11,12,14,15,17,18,
 21,23,24,26,27, & 28, 10" X 10" DROP
 DOWN FROM SECOND FLOOR INTO GARAGE AREA
 THEN BACK INTO THE FIRST FLOOR.THIS IS
 A RATED WALL & FLOOR ASSEMBLY.DUCT
 CANNOT EXCEED 100 SQ IN AND SHALL COMPLY
 WITH ALL OF 2001 FBC(M) 607.1.3 #3 ITEMS
 1 THRU 4.WHERE THE 8" DUCT PENETRATES
 FROM THE GARAGE INTO THE "FOYER" THIS
 DUCT SHALL ALSO COMPLY WITH THE AFORE-
 MENTIONED CODE.
  
 DRYER EXHAUST WAS NOT ADDRESSED.MAX
 DEVELOPED LENGTH OF 25 FT WITH A 5 FT
 REDUCTION FOR EACH 90 DEGREE RAD &
 2 1/2 FT REDUCTION FOR EACH 45 DEGREE
 RAD.
  
 PLEASE CLARIFY PLAN SHEET AC-2.28, POOL
 CABANA FLOOR PLAN - DETAIL INDICATES THE
 CONDENSING UNIT UPSTAIRS, THE ARCH PLAN
 SHEET A.45.01 INDICATES THIS TO BE THE
 AHU.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.