| 2003-01-13 00:00:00 | DENIED: |
| | |
| | 1.PROVIDE OUTSIDE AIR CALCULATION AS |
| | PER 2001 FBC(M) TABLE 403.3 OR 402.2 FOR |
| | NATURAL VENTILATION.INDICATE OUTSIDE |
| | AIR ON PLAN, INDICATE DUCT MATERIAL, |
| | SIZE, AND LAYOUT. |
| | |
| | 2.ALL MASTER BATHROOMS INDICATE AN |
| | EXHAUST FAN IN THE TOILET ROOM ONLY. |
| | AS PER 2001 FBC(M) 402.3.1, ROOMS |
| | CONTAINING BATHTUBS SHOWERS OR SPAS |
| | SHALL BE MECHANICALLY VENTILATED. |
| | |
| | 3.PLAN SHEET AC-2.4 & AC-2.5, DO NOT |
| | INDICATE AN EXHAUST FAN IN THE 2ND FLOOR |
| | PDR ROOM. |
| | |
| | 4.EXHAUST FAN SCHEDULE NOR PLAN SHOW |
| | GRILLE SIZE FOR EHXAUST FANS 4 & 5. |
| | |
| | 5.UNITS 9,20,11,12,14,15,21,23,24,26, |
| | 27,28,29, & 30 DO NOT INDICATE MAKE-UP |
| | AIR FOR THE BATHROOMS (MASTER BATHROOMS |
| | DO INDICATE MAKE-UP AIR, OTHER BATHROOMS |
| | DO NOT). PLEASE INDICATE HOW REQUIREMENT |
| | FOR MAKEUP AIR WILL BE ACHIEVED. 2001 |
| | FBC(M) 501.4. |
| | |
| | 6.PLEASE NOTE, DRYERS EXHAUSTING MORE |
| | THAN 200 CFM SHALL HAVE MAKE-UP AIR AS |
| | PER 2001 FBC(M) 504.5. |
| | |
| | 7.PLEASE NOTE, DEVELOPED LENGTH SHALL |
| | NOT EXCEED 25 FT WITH A 5 FT REDUCTION |
| | FOR EACH 90 DEGREE RAD. & A 2 1/2 FT |
| | REDUCTION FOR EACH 45 DEGREE RAD. 2001 |
| | FBC(M) 504.6. |
| | |
| | 8.PLANS DO NOT GIVE SPECIFIC DEMINSION |
| | FOR ACCESS & CLEARANCE FOR SERVICE FOR |
| | THE AHU'S LOCATED IN THE ATTIC.PLEASE |
| | SHOW COMPLIANCE WITH 2001 FBC(M) 306.3 & |
| | 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 FOR |
| | REQUIRED CLEARANCES & ACCESS. |
| | |
| | PLEASE NOTE, ALL AHU'S ARE REQUIRED TO |
| | HAVE AN AUXILLIARY DRAIN PAN WITH OVER |
| | FLOW PROTECTION.2001 FBC(M) 307.2.3. |
| | |