2003-01-13 00:00:00DENIED:
  
 1.PROVIDE OUTSIDE AIR CALCULATION AS
 PER 2001 FBC(M) TABLE 403.3 OR 402.2 FOR
 NATURAL VENTILATION.INDICATE OUTSIDE
 AIR ON PLAN, INDICATE DUCT MATERIAL,
 SIZE, AND LAYOUT.
  
 2.ALL MASTER BATHROOMS INDICATE AN
 EXHAUST FAN IN THE TOILET ROOM ONLY.
 AS PER 2001 FBC(M) 402.3.1, ROOMS
 CONTAINING BATHTUBS SHOWERS OR SPAS
 SHALL BE MECHANICALLY VENTILATED.
  
 3.PLAN SHEET AC-2.4 & AC-2.5, DO NOT
 INDICATE AN EXHAUST FAN IN THE 2ND FLOOR
 PDR ROOM.
  
 4.EXHAUST FAN SCHEDULE NOR PLAN SHOW
 GRILLE SIZE FOR EHXAUST FANS 4 & 5.
  
 5.UNITS 9,20,11,12,14,15,21,23,24,26,
 27,28,29, & 30 DO NOT INDICATE MAKE-UP
 AIR FOR THE BATHROOMS (MASTER BATHROOMS
 DO INDICATE MAKE-UP AIR, OTHER BATHROOMS
 DO NOT). PLEASE INDICATE HOW REQUIREMENT
 FOR MAKEUP AIR WILL BE ACHIEVED. 2001
 FBC(M) 501.4.
  
 6.PLEASE NOTE, DRYERS EXHAUSTING MORE
 THAN 200 CFM SHALL HAVE MAKE-UP AIR AS
 PER 2001 FBC(M) 504.5.
  
 7.PLEASE NOTE, DEVELOPED LENGTH SHALL
 NOT EXCEED 25 FT WITH A 5 FT REDUCTION
 FOR EACH 90 DEGREE RAD. & A 2 1/2 FT
 REDUCTION FOR EACH 45 DEGREE RAD. 2001
 FBC(M) 504.6.
  
 8.PLANS DO NOT GIVE SPECIFIC DEMINSION
 FOR ACCESS & CLEARANCE FOR SERVICE FOR
 THE AHU'S LOCATED IN THE ATTIC.PLEASE
 SHOW COMPLIANCE WITH 2001 FBC(M) 306.3 &
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 FOR
 REQUIRED CLEARANCES & ACCESS.
  
 PLEASE NOTE, ALL AHU'S ARE REQUIRED TO
 HAVE AN AUXILLIARY DRAIN PAN WITH OVER
 FLOW PROTECTION.2001 FBC(M) 307.2.3.
  