Plan Review Notes
Plan Review Notes For Permit 02121272
Permit Number 02121272
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-01-16 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING,AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED FOR
 FIRE AND PARAMEDICAL EQUIPMENT DURING
 CONSTRUCTION.
  
 3) ENSURE ALL GARAGE DOORS INSTALLED IN
 RATED SEPARATION WALLS ARE LABELED AND
 RATED.
  
 4) PROVIDE PORTABLE FIRE EXTINGUISHERS.
  
 5) FIRE LINES ARE NOT ALLOWED TO BE RUN
 UNDERNEATH BUILDING FOUNDATIONS.
  
 6) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER SYSTEM INSTALLATIONS.
  
 7) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM SYSTEM EQUIPMENT.
  
 8) PROVIDE SEPARATE PLANS AND PERMITS
 FOR SECURITY GATES.
  
 9) ALL SMOKE DETECTORS ARE TO BE
 INSTALLED A MINIMUM OF THREE FEET FROM
 AC DIFFUSERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910