| 2003-01-22 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE RISER HC & HB, PLEASE |
| | SEE 3-3/0` IN 1 1/4" CONDUIT. PLEASE SEE |
| | CONDUIT FILL IN NEC. |
| | |
| | 2)NOTE: PLEASE SEE 210-52G FOR MISSING |
| | RECEPT IN GARAGE. PLEASE ALSO SEE 210-8 |
| | FOR GFI PROTECTION. #`S1,4,3,8 |
| | SOME UNITS SHOW REC, BUT NOT GFI. |
| | 3)NOTE: PLEASE CLARIFY ELEVATOR SHOWN |
| | ON PANEL SCHEDULE AND CAN NOT FIND ON |
| | PLANS.?? |
| | |
| | 4)NOTE: PLEASE SEE SOME UNITS MISSING |
| | RECEPTS PER 210-52E SHOWS FRONT BUT NOT |
| | REAR? |
| | |
| | 5)NOTE: ALL RECEOTS SERVING KITCHEN |
| | COUNTERSPACE ARE TO BE SHOWN AS GFI/GFI |
| | PROTECTED PER 210-8-A-6. |
| | |
| | 6)NOTE; PLEASE SIZE GROUNDING ELECTRODE |
| | CONDUCTOR PER 250-66. (3/0`S). SEC. |
| | |
| | 7)NOTE: PLEASE SEE 680-70 FOR REQ`D GFI |
| | PROTECTION OF SPA -TUB SHOWN. PLEASE |
| | INDICATE ON PLANS. |
| | |
| | 8)NOTE: PLEASE CLARIFY ELEVATOR CAR LTS |
| | BEING SHOWNAS "GFI" ON PANEL SCHEDULE? |
| | |
| | 9)NOTE: PLEASE CLARIFY SUB-PANEL BEING |
| | SHOWN AS 200A MCB ON PANEL AND 125 MLO |
| | ON RISER. (E-2.7) |
| | |
| | 10)NOTE: PLEASE SEE OCP AND MIN SIZE |
| | AWG FOR 1OKW HEAT/AHU ON 2.21. PLEASE |
| | SEE 424-3B MIN 125% |
| | |
| | 11)NOTE: PLEASE SEE AWG FOR AHU IN PANEL |
| | HA, #12 W/30A OCP? |
| | |
| | 12)NOTE: PLEASE SHOW ALL CONTINUOUS LOAD |
| | -S ON HOUSE PANELS AT 125%. 215-3,230-42 |
| | ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |