| 2002-12-27 00:00:00 | PLANS SUBMITTED & FILED WITH BUIDLING | | | PERMIT # 02100787 | | | | | | PROVISO: | | | EXHAUST OUTLETS SHALL BE LOCATED NOT | | | LESS THAN 10 FT HORIZONTALLY FROM PARTS | | | OF THE SAME OR CONTIGUOUS BUILDINGS, | | | ADJACENT PROPERTY LINES & AIR INTAKE | | | OPENINGS. 2001 FBC(M) 506.3.14.3. | | | | | | EXHAUST FANS SHALL BE A HINGED UPBLAST | | | AS PER NFPA 96 4-8.2.1 (E). |
|