| Plan Review Notes For Permit 02121251 |
| Permit Number |
02121251 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-06 00:00:00 | ********** NOTES REDLINED ********* | | | | | | PLANS TITLE READS FL ELEC CODE 2001, | | | PLEASE NOTE THERE IS NO SUCH CODE AND | | | WE ARE UNDER 99 NEC. | | | | | | PLEASE ALSO SEE PLANS FOR NOTE, ALL | | | CIRCUITING IS TO BE PLACED ON PLANS | | | AND CORRELATE WITH A PANEL SCHEDULE AND | | | SUBMIT REVISION BEFORE FINAL ELECTRICAL | | | INSPECTION OS CALLED IN. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|