2003-05-27 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THERE ARE 12 CIRCUITS IN PANEL "A" AND
 6 CIRCUITS IN PANEL"B"SCHEDULES THAT
 ARE EITHER DUPLICATED OR DO NOT
 CORRELATE WITH THE CIRCUITS NUMBERS ON
 THE DRAWING AT THE CIRCUIT LOCATION.
  
 PLEASE CORRELATE THE SCHEDULES WITH
 ACTUAL JOB CONDITIONS AND RESUBMIT FOR
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW