Plan Review Notes
Plan Review Notes For Permit 02121233
Permit Number 02121233
Review Stop E
Sequence Number 4
Notes
Date Text
2003-05-05 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE LOADS/PANELS/
 AND DISC`S.
 PLEASE INCREASE SERVICE TO MEET LOAD
 SERVED.
 SHOWS 204A`S ON 150A FUSES AND 200A DISC
 .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]