Plan Review Notes
Plan Review Notes For Permit 02121233
Permit Number 02121233
Review Stop P
Sequence Number 2
Notes
Date Text
2003-02-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) ROUTE PLANS TO DEPT. OF BUSINESS
 REGULATION FOR REVIEW AND APPROVAL.
 PLANS TO BE STAMPED AND WORKSHEET ATT-
 ACHED PRIOR TO RESUBMITTING TO CITY FOR
 REVIEW.
 2) SHT A4.0 HOOD DRAIN SHALL NOT BE PVC.
 PIPE DRIECT TO VENT AND INSTALL A VALVE.
 3) SHT A4.0 RPZ BACKFLOW SHALL BE MAXI-
 MUM OF 4' AFF FOR TESTING AND SERVICING
 4) FROM PREVIOUS REVIEW: SHT A4.0 FLOOR
 PLAN AND SANITARY RISER DIAGRAM, DISH-
 WASHER SHALL DRAIN TO SANITARY. UTILITY
 ORD.
 5) FROM PREVIOUS REVIEW: PLEASE PROVIDE
 DETAILS FOR HDCP TOILET ROOMS PER SEC.
 11-4.22 AND ALL SUBSECTIONS. CLEAR FLOOR
 SPACE NOT SHOWN OR 5' TURNING SPACE.
 6) FROM PREVIOUS REVIEW: GREASE TRAP
 DETAIL ON SHT A4.0 IS NOT APPROVED. SEE
 ATTACHED SHEET FOR CITY UTILITY APPROVED
 DETAIL.
 7) FOR GAS PERMIT APPLICATION THESE
 REQUIREMENTS ARE NOT ADDRESSED FROM PRE-
 VIOUS REVIEW:
 A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 B. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 8) PLEASE SUBMIT A FLOOR PLAN THAT HAS
 MEASUREMENTS FOR TOILET ROOMS.
 9) PAGES ON PLANS DO NOT MATCH INDEX ON
 COVER SHEET. WHEN RESUBMITTING PLANS
 PLEASE SUBMIT TWO FULL SETS WITH PAGES
 SHOWN ON INDEX. REMOVE ALL REVISED
 SHEETS AND INSERT NEW SHEETS. SUBMIT SET
 OF OLD SHEETS TO COMPARE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377