| Date |
Text |
| 2003-02-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) ROUTE PLANS TO DEPT. OF BUSINESS |
| | REGULATION FOR REVIEW AND APPROVAL. |
| | PLANS TO BE STAMPED AND WORKSHEET ATT- |
| | ACHED PRIOR TO RESUBMITTING TO CITY FOR |
| | REVIEW. |
| | 2) SHT A4.0 HOOD DRAIN SHALL NOT BE PVC. |
| | PIPE DRIECT TO VENT AND INSTALL A VALVE. |
| | 3) SHT A4.0 RPZ BACKFLOW SHALL BE MAXI- |
| | MUM OF 4' AFF FOR TESTING AND SERVICING |
| | 4) FROM PREVIOUS REVIEW: SHT A4.0 FLOOR |
| | PLAN AND SANITARY RISER DIAGRAM, DISH- |
| | WASHER SHALL DRAIN TO SANITARY. UTILITY |
| | ORD. |
| | 5) FROM PREVIOUS REVIEW: PLEASE PROVIDE |
| | DETAILS FOR HDCP TOILET ROOMS PER SEC. |
| | 11-4.22 AND ALL SUBSECTIONS. CLEAR FLOOR |
| | SPACE NOT SHOWN OR 5' TURNING SPACE. |
| | 6) FROM PREVIOUS REVIEW: GREASE TRAP |
| | DETAIL ON SHT A4.0 IS NOT APPROVED. SEE |
| | ATTACHED SHEET FOR CITY UTILITY APPROVED |
| | DETAIL. |
| | 7) FOR GAS PERMIT APPLICATION THESE |
| | REQUIREMENTS ARE NOT ADDRESSED FROM PRE- |
| | VIOUS REVIEW: |
| | A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | B. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 8) PLEASE SUBMIT A FLOOR PLAN THAT HAS |
| | MEASUREMENTS FOR TOILET ROOMS. |
| | 9) PAGES ON PLANS DO NOT MATCH INDEX ON |
| | COVER SHEET. WHEN RESUBMITTING PLANS |
| | PLEASE SUBMIT TWO FULL SETS WITH PAGES |
| | SHOWN ON INDEX. REMOVE ALL REVISED |
| | SHEETS AND INSERT NEW SHEETS. SUBMIT SET |
| | OF OLD SHEETS TO COMPARE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |