| 2003-01-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) PLEASE CONTACT RODNEY COMPO, INVIRON- |
| | MENTAL COMPLIANCE TO SIZE GREASE TRAP. |
| | UTILITY DEPT WASTE ORD. #2938-96. PH # |
| | (561) 837-4074 |
| | 2) SHT A4.0 HOOD DRAIN, SAFE WASTE NOT |
| | APPROVED. FLOOR SINK REQUIRED WITH VENT, |
| | OR RUN SEPARATE LINE FROM MAIN VENTED |
| | LINE TO FLOOR SINK. |
| | 3) PLEASE SUBMIT INFORMATION FOR UTILITY |
| | FAN DRAIN. |
| | 4) SHT A4.0 GREASE TRAP DETAIL, SEE |
| | ATTACHED SHEET FOR CITY WEST PALM BEACH |
| | STANDARD FOR GREASE TRAPS. NOTE: 2 WAY |
| | CLEANOUTS REQUIRED ENTERING AND EXITING |
| | GREASE TRAP. SEE WALL AND BOTTOM THICK- |
| | NESS ECT. |
| | 5) RPZ BACKFLOW REQUIRED ON WATER SERV- |
| | ICE TO SPACE. |
| | 6) SHT A4.0 WATER RISER DIAGRAM, WATER |
| | HAMMERS REQUIRED BY SEC 604.9 SHALL BE |
| | SHOWN AND LOCATED NEAR FIXTURE. (ICE |
| | MAKER - DISHWASHER - QUICK CLOSING VAL- |
| | VES). |
| | 7) SHT A4.0 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL IS REQUIRED PER SEC. |
| | 607.3.2 |
| | 8) SEPARATE GAS PERMIT REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR |
| | PERMIT APPLICATION. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | 9) SHT A4.0 DISHWASHER SHALL DRAIN TO |
| | SANITARY PER UTILITY DEPT ORDINANCE. |
| | 10) PLEASE PROVIDE DETAILS FOR HDCP |
| | TOILET ROOMS PER SEC 11-4.22 AND ALL |
| | SUBSECTIONS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |