| Notes |
| Date |
Text |
| 2003-01-10 00:00:00 | DENIED: | | | | | | PLEASE INDICATE ON PLAN THE LOCATION | | | OF THE FRESH AIR INTAKE.AS PER 2001 | | | FBC(M) 401.5.1, OUTSIDE AIR INTAKE | | | OPENINGS SHALL BE LOCATED A MINIMUM OF | | | 10 FT FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, STREETS, | | | ALLEYS, PARKING LOTS & LOADING DOCKS. | | | | | | CLARIFY NOTE ON PLAN "CONNECT TO HEAT | | | HOOD DUCT", THIS APPEARS TO BE TIED INTO | | | TOILET EXHAUST? | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | AS PER NFPA 4-4.4.3. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | GREASE DUCT, FIRE SUPRESSION & WALK-IN | | | COOLER/FREEZER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|