Plan Review Notes
Plan Review Notes For Permit 02121233
Permit Number 02121233
Review Stop M
Sequence Number 1
Notes
Date Text
2003-01-10 00:00:00DENIED:
  
 PLEASE INDICATE ON PLAN THE LOCATION
 OF THE FRESH AIR INTAKE.AS PER 2001
 FBC(M) 401.5.1, OUTSIDE AIR INTAKE
 OPENINGS SHALL BE LOCATED A MINIMUM OF
 10 FT FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, STREETS,
 ALLEYS, PARKING LOTS & LOADING DOCKS.
  
 CLARIFY NOTE ON PLAN "CONNECT TO HEAT
 HOOD DUCT", THIS APPEARS TO BE TIED INTO
 TOILET EXHAUST?
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 AS PER NFPA 4-4.4.3.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 GREASE DUCT, FIRE SUPRESSION & WALK-IN
 COOLER/FREEZER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.