| 2003-01-02 00:00:00 | 1) PLEASE INDICATE HOW MANY EMPLOYEES | | | ARE EXPECTED TO BE PRESENT DURING | | | NORMAL BUSINESS HOURS. | | | | | | 2) COULD NOT LOCATE ANY FIRE ALARM | | | EQUIPMENT CONTAINED WITHIN TENANT | | | SPACE. | | | | | | 3) DOOR SCHEDULE MAKES REFERENCE TO | | | DEADBOLT LOCKS. PLEASE ADVISE IF THESE | | | ARE SINGLE CYLINDER OR DOUBLE CYLINDER | | | LOCKS. LOCKING DEVICES ON EXIT DOORS | | | THAT REQUIRE THE USE OF A KEY ARE | | | PROHIBITED. | | | | | | 4) COULD NOT LOCATE ANY FIRE ALARM | | | EQUIPMENT WITHIN TENANT SPACE. | | | | | | 5) PLEASE INDICATE LOCATIONS OF | | | PORTABLE FIRE EXTINGUISHERS. | | | | | | 6) IT APPEARS THAT ONLY ONE EMERGENCY | | | LIGHT FIXTURE IS PRESENT WITHIN THE | | | SPACE. THIS DOES NOT APPEAR TO BE | | | ACCEPTABLE. | | | | | | 7) COMPLETE PLANS AND PERMIT FOR HOOD, | | | DUCT, AND EXTINGUISHING SYSTEM PLANNED | | | FOR USE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|